Insulation resistance testing

You apply a d.c. test voltage between conductors and measure how much leaks through the insulation. Damaged, damp or crushed insulation shows up as a low reading.

CONSUMER UNITLNEisolated · locked offRest of the circuit✗ lamps out✗ appliances unplugged✗ dimmers, SPDs and electronicsdisconnected>299 MΩMΩ 500 VINSULATION TESTERTest each pair:L–NL–EN–E230 V circuit → 500 V d.c. test voltage
Disconnect anything that could be damaged by the test voltage or give a false low reading. A low reading means damaged or damp insulation somewhere on the circuit.

Why it matters

Insulation that leaks current can cause electric shock, fires and nuisance RCD tripping. It’s also the test most likely to damage equipment if you don’t prepare properly.

Test voltages and minimum values

BS 7671 Table 64 (as amended):

Circuit nominal voltageTest voltage (d.c.)Minimum insulation resistance
SELV and PELV250 V0.5 MΩ
Up to and including 500 V (incl. FELV)500 V1 MΩ
Above 500 V1000 V1 MΩ

A healthy domestic circuit usually reads hundreds of MΩ — many testers show >299 MΩ or >999 MΩ. A reading that passes but is much lower than similar circuits is worth investigating.

Before you test

Method

  1. Line to neutralTest between live conductors.
  2. Line to earthTest each live conductor to the cpc.
  3. Neutral to earthTest neutral to cpc. On three-phase circuits, test every combination.
  4. RecordRecord the lowest live–live and the lowest live–earth reading on the schedule, then reconnect everything you disconnected.
Practise this test in 3D — free

iZapp’s 3D Testing Bench lets you do this test on a virtual board with real-looking kit: place the probes, read the tester and record the result on a practice schedule. Some attempts have a fault planted for you to find.

Frequently asked questions

What is the minimum insulation resistance for a 230 V circuit?

1 MΩ, tested at 500 V d.c. (BS 7671 Table 64).

Why do I need to disconnect equipment first?

The test voltage can damage electronic equipment, and connected loads can give a falsely low reading.

How do I record an over-range reading?

Record it as the tester shows it, for example >299 MΩ or >999 MΩ.

Last updated 2026-10-14. Training summary of BS 7671 and IET Guidance Note 3 practice, written by NAPIT-registered electricians. Always check the current edition and amendment of BS 7671 and your scheme’s requirements.