EICR codes explained: C1, C2, C3 and FI

Every observation on an Electrical Installation Condition Report gets a code. The codes decide whether the installation is satisfactory — and how urgently the client needs to act.

The four codes

CodeMeaningAction
C1Danger present. Risk of injury.Immediate remedial action. Make it safe before leaving — isolate the circuit and tell the person responsible.
C2Potentially dangerous.Urgent remedial action required.
C3Improvement recommended.Not dangerous; doesn’t make the report unsatisfactory on its own.
FIFurther investigation required without delay.Something couldn’t be fully assessed during the inspection and needs investigating.

Satisfactory or unsatisfactory?

If the report has any C1, C2 or FI, the overall condition is unsatisfactory. A report with only C3s (or no observations) can be satisfactory.

Typical examples

ExampleUsual code
Exposed live parts that can be touched (e.g. broken accessory)C1
Incorrect polarityC1 or C2 depending on the risk
No RCD for additional protection on sockets likely to supply outdoor equipmentC2
Absence of main protective bonding to incoming gas or waterC2
Zs exceeds the maximum for the protective deviceC2
No RCD protection on cables concealed in walls (installed to an older edition)C3 (in many cases)
Lack of a surge protective deviceC3 (in many cases)
Circuit that couldn’t be traced or testedFI

Coding is a matter of the inspector’s judgement for the specific situation. Industry guidance such as Electrical Safety First’s Best Practice Guide 4 gives detailed examples.

Code EICRs on your phone

iZapp’s EICR app has observation coding built in, with a regulation library and PDF certificates you can send straight to the client.

Frequently asked questions

Does a C3 fail an EICR?

No. C3 means improvement recommended. On its own it doesn’t make the report unsatisfactory.

What makes an EICR unsatisfactory?

Any C1, C2 or FI observation.

What should I do with a C1?

Make the danger safe immediately — usually by isolating the affected part — and tell the person responsible, ideally in writing with a danger notification.

Last updated 2026-10-14. Training summary of BS 7671 and IET Guidance Note 3 practice, written by NAPIT-registered electricians. Always check the current edition and amendment of BS 7671 and your scheme’s requirements.