Safe isolation procedure: step-by-step guide

Safe isolation is the most important thing you will ever learn as an electrician. Get it right every time and you go home every time. This is the standard UK procedure, in order, with the test combinations and equipment you need.

Never assume a circuit is dead. Under the Electricity at Work Regulations 1989, work on or near live conductors is only allowed in very limited circumstances. Isolate, prove dead and secure the isolation first.

What you need

The safe isolation procedure

  1. Identify the circuit or equipmentUse drawings, charts and labels to find the correct point of isolation. Get permission to isolate and warn anyone affected.
  2. IsolateSwitch off at the correct isolator, switch-disconnector or circuit breaker. A functional switch is not a means of isolation.
  3. Secure the isolationLock it off, keep the key on your person, and fit a warning notice. If the device can't be locked, remove fuses or use another secure method.
  4. Prove the voltage indicatorCheck it works on the proving unit or a known live supply.
  5. Test that the circuit is deadTest between every combination of live conductors and earth at the point of work (see the tables below).
  6. Re-prove the voltage indicatorProve it again on the proving unit to show it was working throughout the test.
  7. Begin workOnly now is it safe to start. If you leave and come back, check the isolation is still in place.

Test combinations

Single-phase (3 tests)

TestBetween
1Line – Neutral
2Line – Earth
3Neutral – Earth

Three-phase (10 tests)

Between linesLines to neutralLines to earthNeutral to earth
L1 – L2L1 – NL1 – EN – E
L1 – L3L2 – NL2 – E
L2 – L3L3 – NL3 – E

GS38 test equipment requirements

HSE guidance note GS38 sets out what test probes and leads should look like to reduce the risk of shock, short circuits and arc flash:

Common mistakes

Drill the sequence — free

Do safe isolation step by step on iZapp’s 3D Testing Bench — prove, isolate, lock off, test dead and re-prove on a virtual board. Free, on your phone.

Frequently asked questions

What is the safe isolation procedure?

It is the method used to make sure a circuit or piece of equipment is dead before you work on it: identify the circuit, isolate it, secure the isolation with a lock and warning notice, prove your voltage indicator on a known source, test that the circuit is dead between all conductors, then re-prove the voltage indicator.

Why do you prove the tester before and after?

Proving the voltage indicator before and after testing shows it was working throughout. If it failed during the test, a "dead" reading could be false — and that is how people get killed.

How many tests are needed on a three-phase supply?

Ten: L1–L2, L1–L3, L2–L3, L1–N, L2–N, L3–N, L1–E, L2–E, L3–E and N–E.

Can I use a multimeter for safe isolation?

No. HSE guidance GS38 recommends a two-pole voltage indicator designed for the job, used with a matching proving unit. Multimeters can be set to the wrong range or fail in ways that give a false dead reading.

What does GS38 say about test probes?

Probes should have finger guards and well-insulated leads, with exposed metal tips of no more than 4 mm (2 mm or less, or spring-loaded retractable tips, are preferred) to reduce the risk of short circuits and arc flash.

Last updated 2026-10-14. This guide summarises standard UK practice and HSE guidance GS38 for training purposes. Always follow your employer's procedures and the current guidance.