Earth fault loop impedance: Ze and Zs

The protective device only disconnects fast enough if the fault current is big enough — and that depends on the impedance of the earth fault loop.

SUPPLYTRANSFORMERORIGINFAULTL to metalZethe supply’s partR1 + R2the circuit’s partline (R1)cpc (R2)Zs = Ze + (R1 + R2)
The lower the loop impedance, the bigger the fault current — and the faster the breaker disconnects.
Ze — at the originIsolate the installation and take theearthing conductor off the MET. Test lineto the earthing conductor. Put it back.Typical max: TN-C-S 0.35 Ω · TN-S 0.8 ΩZs — at the furthest pointLive: L–E at each outlet (use the no-tripsetting on RCD circuits). Record the highest,check it’s close to Ze + (R1+R2), thencompare with 80% of the device’s max Zs.e.g. B32: max 1.37 Ω → 1.10 Ω
Prospective fault current (Ipf) is measured at the origin too: L–N and L–E, record the higher.

Ze — at the origin

Ze is the part of the loop outside the installation. Measure it at the origin between line and the main earthing conductor, disconnected from the MET so parallel paths through bonding don’t lower the reading — and reconnect it straight after. Typical maximum values declared by distribution network operators:

Earthing arrangementTypical maximum Ze
TN-C-S (PME)0.35 Ω
TN-S0.8 Ω
TT21 Ω (supply side only — the installation earth electrode is extra)

Zs — at the furthest point

Zs is the whole loop. Measure it live at the furthest point of each circuit, line to earth, or calculate it as Zs = Ze + (R1+R2). On RCD-protected circuits use the tester’s no-trip (low-current) loop setting.

Always cross-check a measured Zs against Ze + (R1+R2). A measured value much higher than the calculated one points to a loose or high-resistance connection.

Comparing with the maximum

BS 7671 Table 41.3 gives maximum Zs for each device. Those values are at conductor operating temperature, so when you test at room temperature compare your reading with roughly 80% of the tabulated value (the rule of thumb used in IET Guidance Note 3). See the max Zs tables.

Prospective fault current (Ipf)

At the origin, also measure PSCC (line–neutral) and PEFC (line–earth). Record the higher as Ipf and check it doesn’t exceed the breaking capacity of the protective devices. For a three-phase supply, a common approximation is twice the line–neutral PSCC.

Practise this test in 3D — free

iZapp’s 3D Testing Bench lets you do this test on a virtual board with real-looking kit: place the probes, read the tester and record the result on a practice schedule. Some attempts have a fault planted for you to find.

Frequently asked questions

What is the difference between Ze and Zs?

Ze is the external earth fault loop impedance at the origin of the installation. Zs is the total loop impedance at a point in a circuit — Ze plus the circuit’s R1+R2.

Why disconnect the earthing conductor to measure Ze?

To remove parallel earth paths through the bonding (gas, water pipes), which would give a falsely low reading. Reconnect it immediately afterwards.

What is the 80% rule?

Tabulated max Zs values assume hot conductors. Testing at room temperature, compare your measured Zs with about 80% of the table value to allow for the rise in resistance.