Module 4 • Insulation Resistance & Polarity
Insulation Resistance Testing
<h2>Purpose of IR testing</h2> <p>Insulation resistance (IR) testing verifies the integrity of the cable insulation between live conductors and between conductors and earth. Degraded insulation allows leakage current to flow — causing shock risk, fire risk and RCD nuisance tripping.</p> <h2>Test voltages and minimum values (BS 7671 Table 61)</h2> <table> <tr><th>Circuit type</th><th>Test voltage</th><th>Minimum IR</th></tr> <tr><td>SELV and PELV</td><td>250V DC</td><td>1 MΩ</td></tr> <tr><td>Up to 500V (all LV)</td><td>500V DC</td><td>1 MΩ</td></tr> <tr><td>Above 500V</td><td>1000V DC</td><td>1 MΩ</td></tr> </table> <h2>Before testing — what to disconnect</h2> <ul> <li><strong>Surge protective devices (SPDs)</strong> — will be destroyed by 500V DC</li> <li><strong>Electronic dimmers</strong> — contain components that cannot withstand test voltage</li> <li><strong>Sensitive electronic equipment</strong> — computers, controllers, smart home devices</li> <li><strong>Lamps and luminaires</strong> on lighting circuits (or short L-N at each fitting)</li> </ul> <p>Regulation 643.3 requires that precautions are taken to prevent damage to equipment.</p> <h2>Test method for a complete installation</h2> <ol> <li>Isolate the supply and verify dead</li> <li>Connect all line and neutral conductors together at the consumer unit (or close all MCBs)</li> <li>Disconnect sensitive equipment</li> <li>Test between all live conductors connected together and earth</li> <li>Also test between line and neutral with earth disconnected</li> </ol> <h2>Interpreting results</h2> <ul> <li><strong>Above 200MΩ</strong> — excellent, new installation</li> <li><strong>1–200MΩ</strong> — satisfactory</li> <li><strong>Below 1MΩ</strong> — unsatisfactory — investigate before energising</li> <li><strong>Very low (less than 0.5MΩ)</strong> — serious fault — do not energise</li> </ul> <h2>Key exam points</h2> <ul> <li>Test voltage for standard LV circuits: 500V DC</li> <li>Minimum result: 1MΩ for all circuit types</li> <li>SPDs MUST be disconnected — they will fail under test voltage</li> <li>IR testing comes AFTER continuity in the CRIPPER sequence</li> <li>Low IR = insulation fault, moisture, or connected equipment — investigate all three</li> </ul>